Adding and Relocating Fire Sprinkler Heads
This application is for adding or relocating ceiling sprinkler heads that need to be performed by a licensed plumber. Plans must comply with the National Fire Protection Association (NFPA) 13 Chapter 23 in its entirety. Systems with Less than 10 Sprinkler Heads of work shall provide a letter on the contractor’s letterhead. The letter must contain the following:
- Name, address, including suite or unit number
- Description of the scope of work
- Number of heads added and relocated
- Head types, including existing heads
- Installation type, i.e. hard pipe or flex pipe
- Copy of the floor plan showing the additional and relocated heads